Water System Details

Community: PAPPAS & COMPANY (MENDOTA)
County: Fresno
Sys. Category: Complete water system only
Agency Name: PAPPAS & CO (MENDOTA)
Ownership: Private
Ownership Type: Private non-PUC reg
Population: 25
Connections: 12
2010 MHI: 52,857
SDAC or DAC: Non-DAC
DAC Classification Source: Calculated

IRWMP: WESTSIDE SJ
Geography: Valley Floor
Location:

Contact Title: Owner
Contact: George Pappas
Phone:
Alt. Contact:
Phone:

H2O Sys. Num.: 1009039
Water Source: Assumed GW
Active Wells Count: -1
Wells Issues?: XXXXX
Issues: SWTR Violation - The Water System has received Citation No. 03-23-10C-050, issued July 12, 2010 for noncompliance the Surface Water Treatment Rule. The System failed to maintain a daily CT ratio of 1.0 or greater for six (6) days in May 2010. - Non-comp

Potential Solutions:

  Water quality sample results for selected constituents. Values shown for water samples collected 2004-2014.
  Raw Water Delivered Water   Raw Water Delivered Water
  Max. Ave. Count Max. Ave. Count   Max. Ave. Count Max. Ave. Count
Arsenic (10 ug/L): 2.70 2.28 4 2.70 2.28 4 Flouride (2 mg/L): 0.13 0.07 4 0.13 0.07 4
DBCP (0.2 ug/L): Perchlorate (6 ug/L): 4.00 2.00 2 4.00 2.00 2
Nitrate as NO3 (45 mg/L): 3.40 2.70 4 3.40 2.70 4 TCE (5 ug/L):
PCB (0.5ug/L): THMs (80 ug/L): 180.00 155.00 180.00 155.00
Uranium (20 pC/L):              

WW Sys. Num.:
Treatment: XXXXX
Design Flow (MGD):

Total Enforcement Actns:
Cat.1 Viol:
Cat. 2 Viol:

Total Viol:

Septic Probs?: XXXXX
Sewer Issues:
Potential Solutions: Funding is needed to initiate a Planning Study to identify appropriate alternatives to resolve the CT Citation. - Study to determine and construction of best improvement plan from among identified options:1) GAC treatment2) Minimizing water age in the distribution system and maximizng reservior turnover3) Treatment optimization and increased DBP precurser removal through enhanced coagulation4) Disinfection dosage and CT ratio optimization5) Alternative disinfectant injection points6) Alternative disinfectants. - Study to determine and construction of best improvement plan from among identified options:1) Add baffles to storage tanks2) New , larger storage tanks with baffles3) Improved filter media for better removal of contaminents
Treatment Comm: XXXXX
SelfHelp Comments: 36000 W CALIFORNIA, Mendota