Error there is more than one entry for Water System Areas.
(Geography, IRWMP, System Category, MHI2010, and DAC calculation are incorrect in database.)
Community: CARUTHERS COMM SERV DIST
County: Fresno
Sys. Category:
Agency Name: CARUTHERS COMM SERV DIST
Ownership: Public (state, federal, local)
Ownership Type: City, County, State owned
Population: 2103
Connections: 681
2010 MHI: 0,000
SDAC or DAC: SDAC
DAC Classification Source: Calculated
IRWMP:
Geography:
Location: Caruthers
Contact Title: Manager
Contact: David McIntyre
Phone:
Alt. Contact:
Phone:
H2O Sys. Num.: 1010039
Water Source: GW
Active Wells Count: 5
Wells Issues?: XXXXX
Issues: 3 of 4 wells exceed arsenic MCL - The recommended project includes construction of a new well and abandonment of existing Wells No. 1 and 4. The existing Well No. 5 would remain in use and the water produced would be piped to the new well site. A new we
Potential Solutions: Upgrade and expand treatment plant, expand disposal facilities
Water quality sample results for selected constituents. Values shown for water samples collected 2004-2014. | |||||||||||||
Raw Water | Delivered Water | Raw Water | Delivered Water | ||||||||||
Max. | Ave. | Count | Max. | Ave. | Count | Max. | Ave. | Count | Max. | Ave. | Count | ||
Arsenic (10 ug/L): | 28.00 | 18.86 | 73 | 28.00 | 18.86 | 73 | Flouride (2 mg/L): | 0.28 | 0.22 | 9 | 0.28 | 0.22 | 9 |
DBCP (0.2 ug/L): | 0.18 | 0.02 | 20 | 0.18 | 0.02 | 20 | Perchlorate (6 ug/L): | 0.00 | 0.00 | 14 | 0.00 | 0.00 | 14 |
Nitrate as NO3 (45 mg/L): | 23.00 | 6.60 | 55 | 23.00 | 6.60 | 55 | TCE (5 ug/L): | 0.00 | 0.00 | 4 | 0.00 | 0.00 | 4 |
PCB (0.5ug/L): | 2 | 2 | THMs (80 ug/L): | 0.00 | 0.00 | 2 | 0.00 | 0.00 | 2 | ||||
Uranium (20 pC/L): | 8.00 | 6.30 | 2 | 8.00 | 6.30 | 2 |
WW Sys. Num.: 273120
Treatment: XXXXX
Design Flow (MGD): 0.37
Total Enforcement Actns: 4
Cat.1 Viol: 22
Cat. 2 Viol: 0
Septic Probs?: XXXXX
Sewer Issues:
Potential Solutions: CSD is conduting planning study to seek solution to resolve arsenic problem. - The existing water supply facilities for Caruthers include four (4) wells, Numbers 1, 3, 4, and 5. Well No. 1 (flow rate of 350 gpm) is not used except in the summer months. The four (4) wells have a pumping capacity of 3050 gpm, which is adequate for the current population. The water from Well No's 3, 4, and 5 have Arsenic levels of 8, 20, and 12 ppb, respectively, with Well No's 4 and 5 being above the new Federal limit of 10 ppb. These existing 2 wells require treatment for Arsenic removal. The arsenic is in the form of arsenite (As III) and must be pre-oxidized to form an arsenate (As V) species for highest removal efficiency. In general, the pH of the water must be reduced to approximately 7.5 to facilitate conversion to arsenate. - Arsenic levels in excess of the MCL in the drinking water for Caruthers Community Service District. - Water service pressure and supply not reliable. - INADEQUATE SUPPLY DURING SUMMER MONTHS - Existing standby power facilities at Well No. 4 has exceeded the design life expectancy and is presently experiencing operational difficulties.
Treatment Comm: XXXXX
SelfHelp Comments: